After one storm, outdoor APs, bridges and even switch ports in the same area fail together. Damage concentrates at network ports, PoE ports and power inlets — the classic surge entry paths.

Likely causes
Ordered from most to least common:

- No equipotential bonding: the enclosure and pole are not earthed, leaving no path for surge energy
- Cable is the main entry path: outdoor cable behaves like an antenna and carries surge indoors
- No protector on the PoE side: surge travels down the PoE run into the switch
- High earth resistance or an over-long earth lead: the discharge path is ineffective
- Units on isolated high points such as standalone poles or roofs are more likely to be struck
Diagnostic steps
Follow in order.

- Map the damage: devices only, or switch ports too? The latter means surge came down the cable
- Inspect earthing: are enclosure, pole and cabinet bonded to one earth electrode, and does resistance meet spec
- Inspect cable routing: is the outdoor run in conduit, is it shielded, is the shield earthed at both ends
- Confirm a surge protector is fitted on the PoE side, mounted close to the device
- Check for a potential difference between separate earth points
Fix and prevent
Fix: complete the equipotential bonding and fit matched surge protectors at both the outdoor device and the switch. Prevent: put earthing and protection hardware in the outdoor project budget rather than treating it as optional, and record earth resistance measurements at handover.